IONDC27161ADMDDN GPL
Device Time: 2022-10-05 22:44:43 Timezone: GMT -06:00
Power AvailabilityVoltage Disturbances
Availability (ppm)999481.38Number of Events Since2020-07-09 15:16:54
Number of 'Nines'3.00Sag/Swell263.00
Eval Time (days)2898284.00
Voltage Harmonics
 THDTOHDTEHD
V11.55 %1.55 %0.00 %
V21.86 %1.86 %0.00 %
V31.88 %1.88 %0.00 %
V4N/A %N/A %N/A %
Current Harmonics
 THDTOHDTEHDK-FactorCrest Factor
I15.96 %5.96 %0.00 %1.131.42
I24.98 %4.98 %0.00 %1.101.48
I36.31 %6.31 %0.00 %1.201.49
I40.00 %0.00 %0.00 %0.000.00
I5N/A %N/A %N/A %N/AN/A

Meter Type 8600Power Measurement
Firmware Version8600V314
Template8600C_V314_FAC_9S_HM_Centro_PQDNPMBUS_CFECTIVA_ENE2021
Serial NumberMT-1102B056-01